Loop Supply Voltage
Any DC supply / loop resistance that maintains 8 to 32 VDC at F4L terminals. F4L is reverse polarity protected.
3 ft long, 2-conductor 22 AWG shielded cable
Test Function
Front panel button (Test Button), when depressed, sets loop current and display to test calibration level, independent of temperature input, to allow testing of system operation. Test Cal level is set by a multiturn potentiometer to any value from 0 to 100% of Full scale output.
Operation of Test Function
The TEST pushbutton on the front of the gauge, when depressed, switches the display and output loop to a preset level determined by the setting of a Test potentiometer. This test mode will allow setup and testing of the current loop and all connected output devices by switching to this test level whenever desired without having to alter the system temperature. To set the test output level, see F4L label for the location of Test potentiometer. Press and hold the front-panel TEST button and adjust the Test potentiometer to set the display and loop current to the desired test level.
Electrical Connection
Connection to the F4L is made with the 2-wire cable at the gage rear. Connect the loop positive supply (+) to the RED lead and tloop negative supply (-) to the BLACK lead. Reversing the connections will not harm the unit, but the F4L will not operate with incorrect polarity.
Never connect the wires to voltage greater than 32 VDC or permanent damage not covered by warranty will result.
Installation and Precautions
Install or remove F4L using wrench on hex fitting only. Do not attempt to tighten by turning housing or any other part of the unit. It is recommended that a thread sealant be used to ensure leak-free operation.
Weight
Approximately 9 ounces
Storage Temperature
-40 to 203oF (-40 to 95oC)
Operating Temperature
-4 to 185oF (-20 to 85oC) |
Controls
Non-interactive zero and span, ±10% range
test calibration level: 0-100% of range
Retransmission zero and span: internal potentiometers
Display
3 readings per second nominal display update rate
3 ½ digit LCD, ½" digit height
|
Output Characteristics
True analog output, not digitized
70 mmillisecond typical response time
If gauge terminal voltage falls below approximately 7.8 VDC erratic operation may occur
Housing
NEMA 4X UV stabilized polycarbonate/ABS case, light gray color
Clear polycarbonate window to protect display
Gasketed rear cover, six captive stainless steel screws
Accuracy (linearity, hysteresis, repeatability)
Standard: ±0.25% of full scale ±1 least significant digit
|