Wessco now manufactures
Stator RTDs
strator rtds sensors hot spot
Contact Us
for Details!!!

loop powered rtd transmitters

All operating power for the F4L unit is supplied by the 4-20 mA current loop. The 2-wire connection allows the F4L to be used as a digital indicating transmmitter in any 4-20 mA current loop application. The output is a continuous analog signal based on the temperature transducer output rather than the display. The output is filtered to improve noise immunity and has a response time of about 70 msec.

Calibration
Display
Adjust the Zero control until the gauge reads zero with the minus sign (-) occasionally flashing. Span calibration should only be attempted if the user has access to a Temperature reference of known accuracy. The quality of the calibration is only as good as the accuracy of the calibration equipment and ideally should be at least four times the F4L's accuracy.

Zero calibration must be done before span calibration. Record readings at three to five points over the range of temperature transmitter and adjust span control to minimiz error and meet specifications.

Loop Voltage
Select a loop power supply voltage and total loop resistance so that when the loop current is 20mA, the F4L will have at least 8 VDC at its terminals. For correct operation and to avoid erratic or erroneous readings, the F4L terminal voltage must not fall below 8 VDC. Too large a loop resistance will cause the unit's output to limit or saturate before reaching its full 20 mA output. The minimum loop supply voltage may be calculated from the formula:
vmin = 8V + (20mA x Total loop resistance)

If the terminal voltage of the F4L falls below about 7.8 VDC, erratic operation may occur. This is an indication that the loop supply/resistance may not allow adequate headroom for reliable operation. This should never occur in normal use. If this does, examine the loop supply/resistance.

powered indicating rtd transmitter digital temperature gauge
2-Wire Loop-Powered
Indicating RTD Transmitter
Reverse Polarity Protected
absolute process instruments cecomp rtd transmitters

Loop Supply Voltage
Any DC supply / loop resistance that maintains 8 to 32 VDC at F4L terminals. F4L is reverse polarity protected.
3 ft long, 2-conductor 22 AWG shielded cable

Test Function
Front panel button (Test Button), when depressed, sets loop current and display to test calibration level, independent of temperature input, to allow testing of system operation. Test Cal level is set by a multiturn potentiometer to any value from 0 to 100% of Full scale output.

Operation of Test Function
The TEST pushbutton on the front of the gauge, when depressed, switches the display and output loop to a preset level determined by the setting of a Test potentiometer. This test mode will allow setup and testing of the current loop and all connected output devices by switching to this test level whenever desired without having to alter the system temperature. To set the test output level, see F4L label for the location of Test potentiometer. Press and hold the front-panel TEST button and adjust the Test potentiometer to set the display and loop current to the desired test level.

Electrical Connection
Connection to the F4L is made with the 2-wire cable at the gage rear. Connect the loop positive supply (+) to the RED lead and tloop negative supply (-) to the BLACK lead. Reversing the connections will not harm the unit, but the F4L will not operate with incorrect polarity.

Never connect the wires to voltage greater than 32 VDC or permanent damage not covered by warranty will result.

Installation and Precautions
Install or remove F4L using wrench on hex fitting only. Do not attempt to tighten by turning housing or any other part of the unit. It is recommended that a thread sealant be used to ensure leak-free operation.

Weight
Approximately 9 ounces

Storage Temperature
-40 to 203oF (-40 to 95oC)

Operating Temperature
-4 to 185oF (-20 to 85oC)

Controls
Non-interactive zero and span, ±10% range
test calibration level: 0-100% of range
Retransmission zero and span: internal potentiometers

Display
3 readings per second nominal display update rate
3 ½ digit LCD, ½" digit height

Output Characteristics
True analog output, not digitized
70 mmillisecond typical response time
If gauge terminal voltage falls below approximately 7.8 VDC erratic operation may occur

Housing
NEMA 4X UV stabilized polycarbonate/ABS case, light gray color
Clear polycarbonate window to protect display
Gasketed rear cover, six captive stainless steel screws

Accuracy (linearity, hysteresis, repeatability)
Standard: ±0.25% of full scale ±1 least significant digit

 

Click here for full detailed product spec sheet

Name:
E-mail:
Company:
Address:
Suite/Apt.:
City:
State:
Zip:
Daytime Phone:
Evening Phone:
Best time to call:
   
Please check which products you are interested in:
Pressure
Temperature
Level
Flow
Heaters
How did you hear about us?
Comments:
Code:

Type in the secret code word: secret code

Absolute Process

houston texas temperature gauges pressure sensor valves