Series UT Ultrasonic Level Transmitters provide reliable, non-contact measurement for liquid level control in tanks and other vessels. Integral electronics generate an ultrasonic pulse which is transmitted through the air space in the tank. The pulse is reflected back to the sensor at the liquid/air interface. From the received echo, the time of flight can be calculated which is directly proportional to the distance of the liquid surface to the sensor.
A continuous 4 to 20 mA output signal is generated and updated every half second. Units feature a fully adjustable zero and span, height and distance mode adjustment, lost echo LED indication, and reverse polarity protection.
|

Noncontact Measurement
±0.25% Accuracy
4-wire
|
Range
10 ft (3 m)
Service
Liquids
Accuracy
±0.25% full scale
Repeatability
1/8" (3.2 mm) typical
Output Signal
4 to 20 mA DC (isolated), 4-wire
Mounting Orientation
Vertical |
Wetted Material
UT 125: CPVC; UT1264: Kynar
Beam Angle
Conicle 12o
Pressure Limits
100 psig (6.9 bar)
Power Requirements
16 to 30 VDC
Process Connection
¾" male NPT
Blind Zone
6" (15 cm) |
Temperature Limits
Sensor: -20 to 160oF (-29 to 71oC)
Electronics: -10 to 170oF (-23 to 77oC) compensated over full range of sensor
Zero and Span Adjustments
Zero: 6" to 114" (15 to 290 cm)
Span: 1" to 120" (2.5 to 305 cm)
Weight
UT125: 5 lb (2.3 kg)
UT1264: 2.0 lb (0.91 kg)
Enclosure Rating
UT125: NEMA 7, cast aluminum
UT1264: NEMA 4X (IP67), ABS plastic
|