Series GS Gap Switch measures liquid levels at a single point and provides a 10A relay output for high or low level alarm, overflow prevention, and pump protection. The Series GS uses ultrasonic wave propagation between the transducer gap to sense the presence or absence of a liquid.
Integral electronics make installation quick and easy. Units can be mounted in either a vertical or horizontal position with no additional calibration required. Gap switch includes a 0.5 second delay and high level failsafe. |

Liquid Level Measurement
1000:1 Wet/Dry Ration
316 SS Wetted Parts
|
Service
Compatible liquids
(1000:1 wet/dry ratio)
Wetted Material
316 stainless steel
Repeatability
2 mm (0.078") typical
Electircal Rating
10A @ 120 VAC resistive
Mounting Orientation
Vertical or Horizontal
Power Requirements
115 VAC, 50/60 Hz (230 VAC optional)
Agency Approval
CE |
Enclosure Rating
Epoxy-coated cast aluminum
NEMA 4 & 7
Pressure Limits
1000 psig (68.9 bar)
Switch Type
DPDT
Conduit Connection
¾" female NPT
Process Connection
¾" male NPT
Delay [On]
0.5 seconds
Immersion Depth
1" (25.4 mm)
Weight
1 lb (453 g)
|
APPLICATIONS |
Monitor and control levels of water, chemicals, lubricants, acids, creams, lotions, beverages or paints in vessels, storage bins, tanks, sumps, etc.
|
|